Question details (Performance) :
1. The vibrating coal grate stops running totally or intermittently.
2. The current of vibrating coal grate motor rises abnormally.
3. The safety clutch of transmission machine of grate or safety pin is broken.
Answer: cause of the problem:
Boiler’s vibrating coal grate is a rotating combustion equipment, due to the bad working conditions, stuck stalling is easily happened and grate failure happens in daily application and ...
An Interlock in the boiler’s control system is a programmed or hardwired condition that forces a device to be in a pre-determined or permissive state before the process can continue.
Depending on design pressure, fuel type, either liquid, gas or solid, all steam boiler require interlocks to sequence the operation and to prevent damage to the boiler. Examples of such devices are High or Low Boiler Drum Water Level, Low Boiler Feed Pump Pressure, High or Low Fuel pressure, High or Low Atomization pressure (oil fired), Proof of Ignition, Proof of Flame, FD and/or ID (solid fuel) Fan Motor Operation or combustion air pressure, Damper or Valve position and High Boiler Steam Pressure as well as O2 and furnace temperature.
Definition of the tph meaning in boiler
When a steam boiler is continuously operated for a long period of time, the amount of steam generated per hour is called the evaporation amount of this boiler, and is usually used in tons per hour (t/h or tph).
A steam boiler is a steam device that uses heated energy or other thermal energy that is converted by the combustion of a fuel to heat the feed water to obtain specified parameters (temperature, pressure) and quality. 1tph means that the boi...
The boiler manhole-lids are mounted from the inside of the boiler so that the boiler pressure will help to keep them tight. Hence the manholes have to be elliptical in shape to make it possible to take the lid out from the boiler.
The circulating pressure of a thermal oil boiler is generated by the driving of the circulating oil pump to the thermal oil circulation. Generally, the working pressure of the thermal oil pump is 4 ~ 8kg / cm2. Actually, the pressure of the thermal oil pump differs from different working conditions.
What are the factors that affect the maximum pressure of thermal oil heater?
1. Pressure of circulating hot oil pump
The pressure of liqu...
Commonly used dust removal equipment of SZL boiler includes multi-tube dust collector, wet scrapper and bag filter.
1. Multi-tube dust collector: XTD type vertical ceramic multi-tube dust collector has the advantages of wear-resistance, high temperature resistance, corrosion resistance, low cost, etc. Its collection efficiency is not less than 95%, resistance is not higher than 900Pa and mainly removed dust granularity is greater than 20um.
Design, manufacture and acceptance of multi-t...
a) Boiler hot water system design should meet the requirements of Code for design of boiler plant GB50041.
b) Steam collecting device should be installed in the highest position of hot water system and the position where is easy to collect steam. Reliable constant pressure measures and circulating water expansion device should also be set to ensure that pressure in system is not lower than the corresponding saturation pressure of outlet water temperature plus 20 °C so as to avoid boiler wat...
The fuels of ZOZEN WNS gas/ oil fired boiler are mainly oil and gas. Oil and gas fuel are supplied to burner by piping conveying.
Oil fuel supply system mainly includes: oil storage tank, daily-used oil tank, oil filling pump and oil filling pipelines.
Oil storage tank: This is used to store oil for boiler combustion. Small capacity oil storage tank usually adopts buried layout and buried tank should be reliably fixed and be guaranteed not be floated by surface water. Oil tank that volume is m...