Biomass steam boilers recover the heat generated during the biomass combustion process to heat the water in the boiler exchanger circuit. The hot water is then diverted to the heating circuit.
Occasionally it is necessary to remove the ashes generated by biomass combustion and clean the burner.
Many situations require one or more back-up boilers, especially those involving residential accommodation. A properly designed and installed biomass boiler will be as reliable as a fossil fuelled boiler, and in this respect the usual rules for specifying back-up boilers should be applied. However, as a biomass boiler is rarely sized to meet the peak load, the back-up boiler usually acts as a peak-topping boiler as well. Hence, it is usual for back-up boilers to be sized to meet the peak load.
1. Primary air fan: after being heated by the air pre-heater, primary air enters into the wind chamber, then into the furnace through wind caps through the air distributor to fluidize particulate materials;2. Secondary air fan: after being heated by the air pre-heater, secondary air enters into the furnace through the secondary air ducts for complete combustion of fuels; the seal air, conveying air and fuel spreading air of the feeding device also adopt secondary air; 3. Circ...
1. Rational air distribution, supply sufficient and rational air by region; 2. Appropriate furnace temperature;3. Suitable air turbulence and mixing in furnace;4. Fuels remain long enough on chain grate and in the furnace;5. Keep a reasonable distance between the fuel hopper and the flame fronts to avoid igniting fuels in the hopper.The biomass-fired boilers are optimally designed according to the characteristics of different biomass fuels. ZOZEN will customize the biomass-fired boiler for ...
For the selection of heat fluid boilers, first step is to determine several parameters: thermal power in the process, the oil temperature, and the use of waste heat.There are several methods for determining the boiler's thermal power:1. Calculation. According to the specific heat capacity of the material to be heated, the heating temperature difference, the processing amount per unit time, etc., the thermal power is equal to the product of the above three points, and the calculation result considers a certain margin amount as the boiler capacity.2. The sum of thermal power in the process equipment can also be used as the basis for the heat power.3. Refer to the experience of the same industry to increase or decrease on the basis of peers.4. If steam heating is used, it can be converted into heat transfer oil of the same tonnage and the capacity is appropriately reduced.The determination of the temperature of the heat transfer oil can be determined according to the characteristics of th
Question details (performance):Black smoke happens during operating. Answer: Fault reason:(1) Insufficient air volume, improper air distribution, low furnace temperature: boiler usually equipped with air preheater, but when the air preheater has leakage, hot air flow doesn't satisfy the need of burning, smoke will happen.(2) In the case of stalling situation in full automatic oil-fired boiler: significant increase of furnace negative pressure, no flame can be seen from the inspection hole, steam pressure and steam temperature drop, the steam flow decreases sharply. The water level drops suddenly and then rises sharply.(3) Incomplete fuel burning: this is the main cause of boiler smoke, in the operation, some combustible gases such as carbon monoxide, hydrogen, methane will be generated in addition to carbon dioxide, sulphur dioxide, water vapor and oxygen, nitrogen, etc. during incomplete combustion. They burn and generate black smoke. Incomplete combustion of fuel will not only lead t
Question details (Performance):There is no feeding machine between hopper and # 0A/B belt, which causes unstable feeding and feeding amount cannot be controlled, during running, big amount material presses on belts which affect normal operation of the belt.Answer: The cause of the problem: Because the toughness of the biomass fuel is bigger, the proportion is small, material level should not be too high, otherwise it will occur block, so conveying system is normally running 24 hours, moving parts are easy to wear and cause high failure rate; also the length of the cut grass is difficult to guarantee its length between 8 ~ 15cm, and it is easy to get stuck in the feed machine before the furnace and it is difficult to clean, which has a great impact on the load of the boiler. Troubleshooting: 1. To reduce wearing and expand the service life of equipment, general motor adopts variable frequency motor, slow down the running speed, to control the rate of fuel feeding, make material's stacki
Question details (Performance):Dust collecting cloth bag damages a lot. Answer: The cause of the problem: As the biomass-fired boiler fuel moisture is high, and bag material is general PPS, which will reduce the base fabric of the bag in the case of high temperature, high humidity, hydrolysis, oxidation, and cause damage; In addition, the fuel moisture is high and it cannot be completely burned in the furnace, so it burns in the dust collector, which is also an important reason for the damage of the cloth bag.Troubleshooting:(1) Design by full consideration of high fuel moisture, choosing the appropriate induced draft fan, if the existing design is not enough then consider change the induced draft fan.(2) If induced air volume is sufficient, a proper distribution of the first and second wind should be considered. Generally, the fuel with high moisture and light quality such as wood chips, straw and wheat straw hood, the secondary air volume should be increased. For bark, miscellaneous