Question details (performance):Black smoke happens during operating. Answer: Fault reason:(1) Insufficient air volume, improper air distribution, low furnace temperature: boiler usually equipped with air preheater, but when the air preheater has leakage, hot air flow doesn't satisfy the need of burning, smoke will happen.(2) In the case of stalling situation in full automatic oil-fired boiler: significant increase of furnace negative pressure, no flame can be seen from the inspection hole, steam pressure and steam temperature drop, the steam flow decreases sharply. The water level drops suddenly and then rises sharply.(3) Incomplete fuel burning: this is the main cause of boiler smoke, in the operation, some combustible gases such as carbon monoxide, hydrogen, methane will be generated in addition to carbon dioxide, sulphur dioxide, water vapor and oxygen, nitrogen, etc. during incomplete combustion. They burn and generate black smoke. Incomplete combustion of fuel will not only lead t
Question details (Performance):There is no feeding machine between hopper and # 0A/B belt, which causes unstable feeding and feeding amount cannot be controlled, during running, big amount material presses on belts which affect normal operation of the belt.Answer: The cause of the problem: Because the toughness of the biomass fuel is bigger, the proportion is small, material level should not be too high, otherwise it will occur block, so conveying system is normally running 24 hours, moving parts are easy to wear and cause high failure rate; also the length of the cut grass is difficult to guarantee its length between 8 ~ 15cm, and it is easy to get stuck in the feed machine before the furnace and it is difficult to clean, which has a great impact on the load of the boiler. Troubleshooting: 1. To reduce wearing and expand the service life of equipment, general motor adopts variable frequency motor, slow down the running speed, to control the rate of fuel feeding, make material's stacki
Question details (Performance):Dust collecting cloth bag damages a lot. Answer: The cause of the problem: As the biomass-fired boiler fuel moisture is high, and bag material is general PPS, which will reduce the base fabric of the bag in the case of high temperature, high humidity, hydrolysis, oxidation, and cause damage; In addition, the fuel moisture is high and it cannot be completely burned in the furnace, so it burns in the dust collector, which is also an important reason for the damage of the cloth bag.Troubleshooting:(1) Design by full consideration of high fuel moisture, choosing the appropriate induced draft fan, if the existing design is not enough then consider change the induced draft fan.(2) If induced air volume is sufficient, a proper distribution of the first and second wind should be considered. Generally, the fuel with high moisture and light quality such as wood chips, straw and wheat straw hood, the secondary air volume should be increased. For bark, miscellaneous
(Question Details) Specific Performance:(1) There are blasting sounds in the furnace, and the furnace chamber is under positive pressure. There is smoke emitted from the combustion chamber in a leakage. In severe cases, the explosion-proof door of the boiler body opens.(2) Drum water level drops rapidly and the feedwater flow rate is not abnormally larger than steam flow. MFT acts when the water level is below -280mm.(3) Drum pressure, steam flow rate, exhaust temperature decrease, smoke temperature difference increases on both sides.(4) The negative pressure at the inlet of the flue and suction fan becomes smaller and the temperature difference between the two sides increased. (5) Smoke temperature decreases at the inlet and outlet of the cyclone separator, and the temperature of the material returned is low.(6) Bed pressure increases, bed materials clean, fluidization poof, bed temperature distributes unevenly and bottom slag discharge difficultly. Answer:cause of failure:(1) Fly ash
Question details (Performance):The steam pipe vibrates violently and has a dull impact sound.Answer: fault reason: There is air in pipeline ; automatic air vent valve is not turned on; or it is out of order. Troubleshooting: Check all the air release valves on the water supply pipe and the air release valves on the top of the boiler tube for gas storage. If the valve fails, it should be replaced immediately.
Question details (Performance):1. The furnace wall at the coal economizer leaks water and steam with abnormal sound.2. The water level in the boiler drops sharply, and the water supply is obviously greater than the evaporation capacity.3. Smoke exhaust temperature and water outlet temperature rise.Answer: Fault reason:1. The water quality does not reach standard, and the oxygen in the water is decomposed into corroded pipe walls when the temperature rises.2. The low feed water temperature and smoke exhaust temperature make the inner and outer wall of the coal economizer pipe produce acid corrosion, or flying ash wear the pipe wall thin. 3. The pipe is blocked by impurities, causing overheating.4. Poor materials, defects in manufacturing, installation and maintenance. Troubleshooting:1. When economizer is slightly broke, it still maintains boiler operation, and the gap seems will not expand rapidly, in this case, load operation should be reduced, and start the spare boiler immediately,
(Question details) Specific performance:The wall thickness of several boiler tubes was significantly reduced in a large area, the remaining wall thickness was 2.0mm, and some furnace tubes were corroded and worn out. Furnace tube wall is covered with a thick layer of uneven scale, the surface of the scale is brick red and black, scale layer is loose, and it is easy to remove the inner wall of the furnace tube, after removing, the furnace tube wall covered with a layer of corrosion pits. There is a thin layer of brick red corrosion on the outer wall of boiler tube, some of which are attached with black adhesive. Answer: Fault reason:1. The boiler is seriously short of water.2. Poor water circulation and uneven combustion.3. The unqualified quality of the boiler water and undemanding chemical supervision make the inner wall of the pipe corrode and scale, causing the pipe overheat and reduction of the strength.4. Due to the presence of impurities and scale, the furnace tube is blocked ins
Question details (performance):A pump in a gas boiler does not transfer oil. Answer: Fault reason:(1) Pump failure.(2) Oil pressure and power are reduced.(3) The oil inlet valve is not sealed.(4) The inlet pipe is not sealed.(5) The interceptor valve is closed.(6) The filter is contaminated.(7) The filter is not sealed.(8) The tubing is not sealed.(9) Pump suck air inlet.(10) The vacuum degree in oil tube is too high.Troubleshooting:(1) Replace with new pump.(2) Remove the inlet valve and clean or replace it.(3) Seal the inlet pipe.(4) Open.(5) Cleaning.(6) Replace the sealing ring.(7) Tighten and exhaust.(8) Clean the filter and valve.