In recent years, with the continuous development of new energy technology, China's energy utilization mode has changed from a single form in the past to various forms now. As a green fuel energy, natural gas is widely praised by all levels of society and widely developed and used. Therefore, gas-fired boilers have also become popular boiler equipment in contemporary society.
As a kind of special equipment, the safe operation of industrial boilers is the key point that every enterprise may pay attention to. Today, let’s talk about the normal water level in boiler operation.
During the normal operation, the steam drum water level maintains 0mm, and the allowable fluctuation range is ±30mm, with the maximum not exceeding ±50mm.
Different boiler types have different weights. The traditional four-ton coal-fired horizontal boiler in China is about 25~30 tons.
ZOZEN Boiler has two series of coal-fired horizontal boilers, which are DZL series and SZL series. The DZL series with the capacity of 4 tons weighs 25 tons, and the SZL series with the capacity of 4 tons weighs 32 tons.
Please do not hesitate to contact us if any.
With the continuous development of economy, as the main heat energy equipment, industrial boilers are widely used. This article discusses the calculation standard of boiler feedwater enthalpy value.
First of all, don't panic. According to the normal shutdown sequence, check whether the fuel, steam and water valves of gas-fired boiler meet the shutdown requirements.
Secondly, close the surface blowdown valve of the gas-fired boiler to prevent other faults of the boiler. Then, quickly close the main steam valve to prevent the gas boiler drum from losing water.
Thirdly, close the deaerator air supply valve, the main power switch and the natural gas valve. The air inlet of the gas-fired boiler burner should not be blocked to reduce the area of the air inlet, and the room ventilation should not be blocked to avoid the formation of toxic and harmful gases.
Different steam pressures correspond to different steam temperatures.
1. The steam temperature of low-pressure boiler is mostly saturation temperature or not higher than 400℃.
2. The outlet pressure of medium-pressure boiler is 3.8 ~ 5.4 MPa, and the commonly used steam temperature is 450℃.
3. The outlet pressure of sub-high pressure boiler is 5.4 ~ 9.8 MPa, and the common steam temperature is 540℃.
Manually close the fuel supply valve, stop the combustion, purge after the program enters, until the end of the purge, stop the program such as burning heavy oil, and enter the line sweeping stage before stopping the combustion, and purge with steam or light oil pipe; Generally, steam purging is used when stopping for a long time.
Generally, it is required that the water temperature shall be reduced to 80℃ to drain the water in the boiler. This is because if the water temperature is high, the temperature in the furnace is still very high, and the metal of the furnace wall and heating surface will still accumulate some heat. After the water is released, there is no working medium in the water wall to cool, which makes the wall temperature rise and the temperature rise is uneven, which is not conducive to the safety of the water wall.