Discharging high-temperature flue gas generated by a biomass-fired boiler efficiently and safely is crucial for boiler operation, environmental compliance, and energy recovery. These gases, if not handled properly, can lead to energy inefficiency and increase the emission of pollutants. ZOZEN Boiler, as a professional industrial boiler manufacturer, incorporates advanced technologies and strategies to manage and utilize high-temperature flue gases from biomass-fired boilers. Here's an overview o...
(Question details) specific performance:The gas boiler is powered on, press start, the motor does not turn. Answer: Fault reason:1. Insufficient pneumatic locking.2. The solenoid valve is not sealing, and there is air leakage at the joint. Check the lock.3. The thermal relay is open.4. At least one of the conditional circuits is not valid (water level, pressure, temperature and to check whether the program controller is energized to start). Troubleshooting:1. Adjust the air pressure to the requested value.2. Clean or repair solenoid valve pipe joint.3. Check whether the component is damaged and motor current by reset.4. Check whether the water level, pressure and temperature exceed the limit.ZOZEN gas-fired boiler adopts automatic control to control the operation, combustion, water level, temperature and steam pressure. In case of such problems, the system will automatically prompt the error code.
Oil-fired hot water boilers are hot water equipment that is widely used in industrial and civil fields. However, sometimes during use, oil-fired hot water boilers may emit a large amount of white smoke. What is the cause of this?
Firstly, the reason for the oil-fired hot water boiler emitting a large amount of white smoke may be incomplete combustion of the boiler. This may be due to insufficient oil supply, poor oil quality, excessive deposits inside the combustion chamber, and other i...
Make-up water rate refers to the proportion of treated water added to the boilers, steam turbine equipment and its thermal systems and participating in the circulation of steam-water systems in the boiler steam volume in the calculation period.
A hot water boiler should be thoroughly inspected at first, including the accessory pipeline. Close the drain valve and open the gauge cock to discharge the air in the boiler.
Boiler water circulation refers to the circulating flow of water and steam-water mixture on the evaporating heating surface of boiler. What is the working principle of the latest water circulation system of boiler?
Deaerator is one of the key equipment in boiler and heating system. With the popularization and development of demineralized water treatment technology, deoxidization of boilers and heating systems becomes more and more important.
Ash accumulation on the heating surface.
The scaling and ash deposition on the water-cooled wall of the furnace and the ash deposition of the superheater, convention tube bundles, economizer and preheater can increase the thermal resistance of the flue gas, weaken the heat transfer, lessen the cooling effect of the flue gas and increase the exhaust gas temperature of the gas-fired boiler.
Too high excess air coefficient.